The Ontario Building Code | Hydraulic Loads on Branches

7.4.10.7. Hydraulic Loads on Branches

(1) No horizontal sanitary drainage pipe of less than 3 in. size shall have a fixture loading in excess of that permitted by Table 7.4.10.7.

Table 7.4.10.7.
Maximum Permitted Hydraulic Load Drained to a Branch

Forming Part of Sentence 7.4.10.7.(1)

Item

Column 1

Size of Branch, in.

Column 2

Maximum Load, fixture units

1.

1 ¼

2

2.

1 ½

4

3.

2

6