7.5.9.3. installation Conditions

(1) Air admittance valves shall not be installed in supply or return air plenums, or in locations where they may be exposed to freezing temperatures.

(2) Air admittance valves shall be installed in accordance with the manufacturer’s installation instructions.

(3) Air admittance valves shall be rated for the size of vent pipe to which they are connected.

(4) Installed air admittance valves shall be,

(a) accessible, and

(b) located in a space that allows air to enter the valve.

(5) Every drainage system shall have one vent that terminates to open airin conformance with Sentence 7.5.6.5.(1).