3.2.2.27. Group A, Division 2, up to 2 Storeys, Sprinklered
(1) A building classified as Group A, Division 2 is permitted to be of combustible construction ornoncombustible construction used singly or in combination, provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 2 400 m2if 1 storey in building heightwith no basement,
(ii) 1 200 m2if 1 storey in building height, or
(iii) 600 m2 if 2 storeys in building height.
In Plain Language
This article sets one of the specific size-and-construction packages available for a Group A, Division 2 buildings building: up to 2 storeys, sprinklered, with area capped at 600-2,400 m² depending on storey count and basement presence, combustible or noncombustible construction. Designers can choose whichever of the several packages in this Subsection best fits the building being planned, trading height and area against construction type, sprinklering, and fire-resistance rating requirements.
This is a plain-language summary of the 2012/2017 Ontario Building Code text above, for general understanding only and not a substitute for the Code. Always confirm current requirements against the 2024 edition (O.Reg. 163/24) or a qualified professional before construction.