The Ontario Building Code | Clearance to Combustible Framing

9.22.9.3. Clearance to Combustible Framing

(1) Not less than a 100 mm clearance shall be provided between the back and sides of a solid fuel-burning fireplace and combustibleframing, except that a 50 mm clearance is permitted where the fireplace is located in an exterior wall.

(2) Not less than a 50 mm clearance shall be provided between the back and sides of the smoke chamber of a solid fuel-burning fireplace and combustibleframing, except that a 25 mm clearance is permitted where the fireplace is located in an exterior wall.

In Plain Language

A minimum clearance to combustible framing must be maintained around the fireplace assembly, as set out in this article, protecting nearby wood structure from the fireplace's heat.