The Ontario Building Code | Hydraulic Loads from Fixtures with Continuous or Semi-continuous Flow
7.4.10.3. Hydraulic Loads from Fixtures with Continuous or Semi-continuous Flow
(1) Except as provided in Sentence (2), the hydraulic load from a fixture that produces a continuous flow, such as a pump or an air-conditioning fixture, is 31.7 fixture units for each litre per second of flow.
(2) Where a fixture or equipment that produces a continuous or semi-continuous flow drains to a storm drainage system, the hydraulic load from the fixtureis 900 litres for each litre per second of flow.
(3) The hydraulic load from a fixture or equipment that produces a semi-continuous flow shall conform to Table 7.4.10.3.
Table 7.4.10.3.
Maximum Permitted Hydraulic Load from Fixtures with Semi-continuous Flows
Forming Part of Sentence 7.4.10.3.(3)
| Item | Column 1 | Column 2 | Column 3 |
|
| Maximum Permitted Flows by Trap Size |
|
|
|
| Trap Size, in. | Flow, L/s | Hydraulic Load, fixture units |
| 1. | 1 ½ | 0.00 - 0.090 | 3 |
| 2. | 2 | 0.091 - 0.190 | 6 |
| 3. | 3 | 0.191 - 0.850 | 27 |
| 4. | 4 | 0.851 - 5.700 | 180 |