3.2.2.14. Rooftop Enclosures

(1) A rooftop enclosure for elevator machinery or for a service room shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.83.

(2) A rooftop enclosure for elevator machinery or for a service room, not more than 1 storeyhigh, is not required to have a fire-resistance rating.

(3) A rooftop enclosure for a stairway shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.83.

(4) A rooftop enclosure for a stairway need not have a fire-resistance rating nor be constructed as a fire separation.

In Plain Language

Rooftop enclosures for elevator machinery or service rooms must match the building's required construction type, though single-storey enclosures don't need a fire-resistance rating; stairway rooftop enclosures follow the same construction-type rule but never need a rating or to be built as a fire separation.