The Ontario Building Code | Group A, Division 3, 1 Storey
3.2.2.34. Group A, Division 3, 1 Storey
(1) A building classified as Group A, Division 3 is permitted to be of combustible constructionor noncombustible construction used singly or in combination, provided,
(a) it is not more than 1 storey in building height, and
(b) it has a building area not more than,
(i) 1 000 m2if facing one street,
(ii) 1 250 m2if facing two streets, or
(iii) 1 500 m2if facing three streets.
In Plain Language
This article sets one of the specific size-and-construction packages available for a Group A, Division 3 buildings building: 1 storey with area capped at 1,000-1,500 m² depending on street frontage, combustible or noncombustible construction. Designers can choose whichever of the several packages in this Subsection best fits the building being planned, trading height and area against construction type, sprinklering, and fire-resistance rating requirements.