The British Columbia Building Code | Section 5.8. | Sound Transmission

Division B: Acceptable Solutions Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
Section 5.8. Sound Transmission
(See NoteA-5.8.)
5.8.1. Protection from Airborne Noise
5.8.1.1. Required Protection
1) Except as provided in Sentence(2), a dwelling unit shall be separated from every other space in a building in
which noise may be generated by
a) a separating assembly and adjoining constructions, which, together, provide an apparent sound transmission
class (ASTC) rating not less than 47, or
b) a separating assembly that provides a sound transmission class (STC) rating of not less than 50 and adjoining
constructions that conform to Article 9.11.1.4.
2) Construction separating a dwelling unit from an elevator shaft or a refuse chute shall have an STC rating not
less than 55.
5.8.1.2. Determination of Sound Transmission Ratings
(See Note A-5.8.1.2.)
1) The STC ratings of separating assemblies shall be determined in accordance with ASTM E 413,
“Classification for Rating Sound Insulation,” using the results from measurements carried out in accordance with
ASTM E 90, “Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements.”
2) The ASTC ratings of separating assemblies and adjoining constructions shall be
a) determined in accordance with ASTM E 413, “Classification for Rating Sound Insulation,” using the results
from measurements carried out in accordance with ASTM E 336, “Measurement of Airborne Sound
Attenuation between Rooms in Buildings,” or
b) calculated in accordance with
i) the detailed method described in Article 5.8.1.4., or
ii) the simplified method described in Article 5.8.1.5.
5.8.1.3. Compliance with Required Ratings
1) Compliance with the required STC ratings shall be demonstrated through
a) measurements carried out in accordance with Sentence 5.8.1.2.(1), or
b) the construction of separating assemblies conforming to those presented in Table 9.10.3.1.-A or9.10.3.1.-B,
as applicable.
2) Compliance with the required ASTC ratings shall be demonstrated through
a) measurements or calculations carried out in accordance with Sentence 5.8.1.2.(2), or
b) the construction of separating assemblies conforming to those presented in Table 9.10.3.1.-A or9.10.3.1.-B,
as applicable, that have an STC rating of not less than 50 in conjunction with flanking assemblies constructed
in accordance with Article 9.11.1.4.
5.8.1.4. Detailed Method for Calculating ASTC
(See NoteA-5.8.1.4.)
1) The sound transmission loss measured in accordance with ASTM E 90, “Laboratory Measurement of
Airborne Sound Transmission Loss of Building Partitions and Elements,” shall be used in lieu of the sound reduction
index required in ISO 15712-1, “Building Acoustics – Estimation of Acoustic Performance of Buildings From the
Performance of Elements – Part 1: Airborne Sound Insulation Between Rooms.”
2) The vibration reduction index for the junctions between separating assemblies shall be
Part 5 – Environmental Separation Division B: Acceptable Solutions
Division B British Columbia Building Code 2018
a) determined using the equations presented in Annex E of ISO 15712-1, “Building Acoustics – Estimation of
Acoustic Performance of Buildings From the Performance of Elements – Part 1: Airborne Sound Insulation
Between Rooms,” or
b) measured in accordance with Parts 1 to 4 of ISO 10848, “Acoustics – Laboratory Measurement of the
Flanking Transmission of Airborne and Impact Sound Between Adjoining Rooms.”
3) The normalized flanking level difference shall be measured in accordance with Parts 1 to 4 of ISO 10848,
“Acoustics – Laboratory Measurement of the Flanking Transmission of Airborne and Impact Sound Between
Adjoining Rooms.”
4) The direct sound reduction index for the separating assembly in situ shall be determined using Clause (a)
or(b), depending on the type of construction:
a) for a lightweight separating wall or floor assembly with wood or steel framing, the index shall be taken as
equal to the sound transmission loss, without correction;
b) for a heavyweight separating wall or floor assembly of concrete or masonry, the index shall be determined in
accordance with the detailed method for structure-borne transmission presented in ISO 15712-1, “Building
Acoustics – Estimation of Acoustic Performance of Buildings From the Performance of Elements – Part 1:
Airborne Sound Insulation Between Rooms.”
5) The flanking sound reduction index for each flanking path at each edge of the separating assembly shall be
determined using Clause (a),(b) or(c), depending on the type of construction:
a) for a lightweight separating wall or floor assembly with wood or steel framing and connected lightweight
flanking assemblies with wood or steel framing, the index shall be taken as equal to the normalized flanking
level difference re-normalized for the ASTC field situation in accordance with Annex F of ISO 15712-1,
“Building Acoustics – Estimation of Acoustic Performance of Buildings From the Performance of Elements –
Part 1: Airborne Sound Insulation Between Rooms”;
b) for a heavyweight separating wall or floor assembly of concrete or masonry and connected flanking assemblies
of concrete or masonry, the index shall be determined in accordance with the detailed method for
structure-borne transmission presented in ISO 15712-1, “Building Acoustics – Estimation of Acoustic
Performance of Buildings From the Performance of Elements – Part 1: Airborne Sound Insulation Between
Rooms”;
c) for a mixture of lightweight framed assemblies and heavyweight concrete or masonry assemblies, the index
shall be determined in accordance with Clause(a) or(b).
6) Once the pertinent indices and measurements referred to in Sentences (1) to(5) have been determined based
on the type of construction, the apparent sound reduction index shall then be determined in accordance with
ISO 15712-1, “Building Acoustics – Estimation of Acoustic Performance of Buildings From the Performance of
Elements – Part 1: Airborne Sound Insulation Between Rooms.”
7) The ASTC shall be calculated in accordance with ASTM E 413, “Classification for Rating Sound Insulation,”
using the apparent sound reduction index determined in Sentence(6), which shall be treated as equivalent to the
values of apparent sound transmission loss measured in accordance with ASTM E 336, “Measurement of Airborne
Sound Attenuation between Rooms in Buildings.”
5.8.1.5. Simplified Method for Calculating ASTC
(See Note A-5.8.1.4.)
1) The STC rating shall be used in lieu of the weighted sound reduction index required in ISO 15712-1,
“Building Acoustics – Estimation of Acoustic Performance of Buildings From the Performance of Elements – Part 1:
Airborne Sound Insulation Between Rooms.”
2) The vibration reduction index for the junctions between separating assemblies shall be
a) determined using the equations presented in Annex E of ISO 15712-1, “Building Acoustics – Estimation of
Acoustic Performance of Buildings From the Performance of Elements – Part 1: Airborne Sound Insulation
Between Rooms,” or
b) measured in accordance with Parts 1 to 4 of ISO 10848, “Acoustics – Laboratory Measurement of the
Flanking Transmission of Airborne and Impact Sound Between Adjoining Rooms.”
Division B: Acceptable Solutions Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
3) The weighted normalized flanking level difference shall be determined in accordance with ASTM E 413,
“Classification for Rating Sound Insulation,” using the results from measurements carried out in accordance with
Parts 1 to 4 of ISO 10848, “Acoustics – Laboratory Measurement of the Flanking Transmission of Airborne and
Impact Sound Between Adjoining Rooms.”
4) The direct weighted sound reduction index for the separating assembly shall be taken as equal to the STC,
without correction.
5) The weighted flanking sound reduction index for each flanking path at each edge of the separating assembly
shall be determined using Clause (a) or (b), depending on the type of construction:
a) for a lightweight separating wall or floor assembly with wood or steel framing and connected lightweight
flanking assemblies with wood or steel framing, the index shall be taken as equal to the weighted normalized
flanking level difference re-normalized for the ASTC field situation in accordance with Annex F of ISO
15712-1, “Building Acoustics – Estimation of Acoustic Performance of Buildings From the Performance of
Elements – Part 1: Airborne Sound Insulation Between Rooms”;
b) for a heavyweight separating wall or floor assembly of concrete or masonry and connected flanking assemblies
of concrete or masonry, the index shall be determined in accordance with the simplified method for
structure-borne transmission presented in ISO 15712-1, “Building Acoustics – Estimation of Acoustic
Performance of Buildings From the Performance of Elements – Part 1: Airborne Sound Insulation
Between Rooms.”
6) Once the pertinent indices and measurements referred to in Sentences (1) to(5) have been determined based
on the type of construction, the ASTC shall then be calculated in accordance with ISO 15712-1, “Building
Acoustics – Estimation of Acoustic Performance of Buildings From the Performance of Elements – Part 1: Airborne
Sound Insulation Between Rooms.”
Division B: Acceptable Solutions Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
3) The weighted normalized flanking level difference shall be determined in accordance with ASTM E 413,
“Classification for Rating Sound Insulation,” using the results from measurements carried out in accordance with
Parts 1 to 4 of ISO 10848, “Acoustics – Laboratory Measurement of the Flanking Transmission of Airborne and
Impact Sound Between Adjoining Rooms.”
4) The direct weighted sound reduction index for the separating assembly shall be taken as equal to the STC,
without correction.
5) The weighted flanking sound reduction index for each flanking path at each edge of the separating assembly
shall be determined using Clause (a) or (b), depending on the type of construction:
a) for a lightweight separating wall or floor assembly with wood or steel framing and connected lightweight
flanking assemblies with wood or steel framing, the index shall be taken as equal to the weighted normalized
flanking level difference re-normalized for the ASTC field situation in accordance with Annex F of ISO
15712-1, “Building Acoustics – Estimation of Acoustic Performance of Buildings From the Performance of
Elements – Part 1: Airborne Sound Insulation Between Rooms”;
b) for a heavyweight separating wall or floor assembly of concrete or masonry and connected flanking assemblies
of concrete or masonry, the index shall be determined in accordance with the simplified method for
structure-borne transmission presented in ISO 15712-1, “Building Acoustics – Estimation of Acoustic
Performance of Buildings From the Performance of Elements – Part 1: Airborne Sound Insulation
Between Rooms.”
6) Once the pertinent indices and measurements referred to in Sentences (1) to(5) have been determined based
on the type of construction, the ASTC shall then be calculated in accordance with ISO 15712-1, “Building
Acoustics – Estimation of Acoustic Performance of Buildings From the Performance of Elements – Part 1: Airborne
Sound Insulation Between Rooms.”