Part 1 – Compliance Division A: Compliance, Objectives and Functional Statements
Division A Revision 2.01 British Columbia Building Code 2018
17 Corridor Width
Article 3.3.1.9., Subsection 3.4.3., Article 9.9.3.3.
Public corridors and exit corridors are permitted to have
a minimum width of 1 100 mm.
Public corridors and exit corridors are permitted with a minimum width of
800 mm provided:
(a) the occupant load of the building is maximum 20 people, and
(b) the building does not exceed 3 storeys in building height.
18 Door Swing
Article 3.3.1.10., Article 3.4.6.12., Article 9.9.6.5.
Doors required to swing in the direction of exit travel.
2nd egress door from a room is not required to swing in the direction of exit
travel provided:
(a) the building is sprinklered and the system is supervised in conformance
with Sentence 3.2.4.9.(3), and
(b) the occupant load of the building is maximum 100 people.
19 Stairs, Ramps, Handrails and Guards
Article 3.3.1.14., Article 3.3.1.16., Article 3.3.1.18.,
Articles 3.4.6.5 to 3.4.6.79., Section 9.8.
Existing conditions that do not comply fully with the requirements are
permitted if they are acceptable to the authority having jurisdiction.
20 Transparent Doors and Panels
Article 3.3.1.19., Article 9.6.1.4.
S
afety glass required.
Existing glass or transparent panels that do not comply fully with the
requirements are permitted if sufficiently discernible or guards are provided
in hazardous situations.
21 Dead-end Corridors
Sentence 3.3.1.9.(7), Article 9.9.7.3.
Dead-end corridors are permitted to a maximum length
of 6 m.
1. Dead-end corridors are permitted to a maximum length of 10 m in
Group C occupancies provided:
(a) the building is sprinklered with fast response sprinklers, and
(b) smoke detectors are installed in the corridor system.
2. Dead-end corridors are permitted to a maximum of 15 m in length in
Group D, E, F, Division 2 and F, Division 3 occupancies provided:
(a) the building is sprinklered with fast response sprinklers, and
(b) smoke detectors are installed in the corridor system.
22 Exits
Article 3.4.2.1., Article 9.9.8.2.
Floor areas shall be served by not fewer than 2 exits
except as permitted by Sentence 3.4.2.1.(2).
Floor areas may be served by a single exit within the limits of Sentence
3.4.2.1.(2) provided:
(a) the building does not exceed 3 storeys in building height,
(b) the building is sprinklered with fast response sprinklers, and
(c) all floor areas are protected by a system of smoke detectors connected
to a fire alarm system.
23 Reduction of Exit Width
Sentence 3.4.3.3.(2), Article 9.9.6.1.
Swinging doors in their swing shall not reduce the
effective width of exit stairs and landings to less than
750 mm.
Existing swinging doors in their swing are permitted to reduce the effective
width of exit stairs and landings to a minimum of 550 mm provided:
(a) they serve Group C or D occupancies,
(b) the building does not exceed 4 storeys in building height, and
(c) the building is sprinklered.
24 Fire Separation of Exits
Article 3.4.4.1., Subsection 9.9.4.
Exits are required to be separated from the remainder of
the floor area by a fire separation having a
fire-resistance rating of not less than required by
Subsection 3.2.2. , but not less than 45 min.
1. Buildings of 3 storeys or less may have exits that are separated by a fire
separation that does not have a fire-resistance rating provided:
(a) the building is sprinklered with fast response sprinklers, and
(b) the sprinkler system is supervised in accordance with Sentence
3.2.4.9.(3).
2. Buildings not exceeding 6 storeys in building height may have exits that
are separated by a fire separation having a fire resistance rating of not less
than 45 min provided the building is sprinklered.
25 Exits Through Lobbies
Article 3.4.4.2., Article 9.9.8.5.
Rooms adjacent to the lobby are required to be
separated by a fire separation.
Rooms adjacent to the lobby are not required to be separated by a fire
separation provided:
(a) the floor area is sprinklered with fast response sprinklers, and
(b) smoke detectors are installed in the adjacent rooms.
26 Rooms Opening into Exit
Sentence 3.4.4.4.(7), Article 9.9.5.9.
Service rooms and ancillary rooms are not permitted to
open directly into an exit.
Service rooms and ancillary rooms may open directly into an exit provided:
(a) the room is sprinklered with fast response sprinklers, and
(b) weatherstripping is installed on the door to prevent the passage of
smoke.
Table 1.1.1.1.(5) (continued)
Alternate Compliance Methods for Heritage Buildings
Forming part of Sentence 1.1.1.1.(5)
No. Code Requirement in Division B Alternate Compliance Method