Division B: Acceptable Solutions Part 3 – Fire Protection, Occupant Safety and Accessibility
British Columbia Building Code 2018 Revision 2.01 Division B
a) are not more than250mm long,
b) comply with the flame-resistance requirements of CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics
and Films,” and
c) are not used in a location where they are exposed to heated air or radiation from heat sources that could cause
the exposed surface temperature to be more than 120°C.
3.6.5.3. Tape
1) Tape used to seal joints in air ducts, plenums and other parts of air duct systems shall meet the
flame-resistance requirements for fabric in CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics and Films.”
3.6.5.4. Coverings, Linings, Adhesives and Insulation
1) Coverings, linings and associated adhesives and insulation for air ducts, plenums and other parts of air duct
systems that would have an exposed surface temperature more than 120°C when exposed to heated air or radiation
from heat sources shall be of noncombustible material.
2) Except as permitted by Sentence(3), combustible coverings and linings, including associated adhesives and
insulation, shall have
a) a flame-spread rating not more than25 on any exposed surface or any surface that would be exposed by
cutting through the material in any direction, and
b) a smoke developed classification not more than50.
3) The outer covering of ducts, plenums and other parts of air duct systems used within an assembly of
combustible construction is permitted to have
a) an exposed surface flame-spread rating not more than75, and
b) a smoke developed classification not more than50.
4) Combustible coverings and linings referred to in Sentences(2) and(3) shall not flame, glow, smoulder or
smoke when tested in accordance with the method of test in ASTM C 411, “Hot-Surface Performance of
High-Temperature Thermal Insulation,” at the maximum temperature to which the coverings and linings are to be
exposed in service.
5) Except as permitted by Sentence(6), foamed plastic insulation shall not be used as part of an air duct system
or for insulating an air duct.
6) Foamed plastic insulation is permitted to be installed in a ceiling space that is used as a return air plenum
provided the foamed plastic insulation is protected from exposure to the plenum in accordance with Article3.1.5.14.
7) Combustible coverings and linings of ducts, including associated adhesives and insulation, shall be interrupted
where the duct penetrates a fire separation and at the immediate area of operation of heat sources in a duct system,
including electric resistance heaters or fuel-burning heaters or furnaces.
3.6.5.5. Insulation and Coverings
1) Insulation and coverings on pipes in which the temperature of the fluid exceeds 120°C shall
a) be made of noncombustible material, or
b) not flame, glow, smoulder or smoke when tested in accordance with ASTMC411, “Hot-Surface
Performance of High-Temperature Thermal Insulation,” at the maximum temperature to which the
insulation or covering is to be exposed in service.
2) Except as permitted by Sentence(5), where
combustible insulation is used on piping in a horizontal service
space or a vertical service space, the insulation and coverings on that piping shall have a flame-spread rating, on any
exposed surface and on any surface that would be exposed by cutting through the material in any direction,
a) not more than25 in a building required to be of noncombustible construction or in a
building or part of a
building permitted to be of encapsulated mass timber construction, or
b) not more than75 in a building permitted to be of combustible construction.